The fan-coil control unit is housed in a 4-module box for DIN rail. Features the following inputs:
• configurable input for bathroom or room window switch, button, timed button, switch;
• input for bathroom or room temperature sensor
• features the following relay outputs with voltage-free contacts for 230Vac, 4(2)A loads:
• Low-speed fan-coil relay;
• Medium-speed fan-coil relay. Alternatively, ON/OFF or timed activation via computer, shutter opening or shutter closing;
• High-speed fan-coil relay. Alternatively, ON/OFF or timed activation via computer, shutter opening or shutter closing;
• hot/cold water solenoid valve relay for 2-tube fan-coil or hot water solenoid valve for 4-tube fan-coil. Alternatively, ON/OFF or timed activation via computer, shutter opening or shutter closing;
• heated towel rail or cold water solenoid valve relay for 4-tube fan coil.
Alternatively, slaved activation, timed slaved activation, shutter opening, shutter closing, activation via button, timed button or switch.
Also features a 0-10Vdc output for controlling radiator modulating valve or fancoil.
Connection to UGC-IP or UGT-IP control unit and other units or panels via RJ12 connectors. 12Vdc power supply directly from UGC-IP or UGT-IP units via RJ12 connector or specific 12Vdc, 3.5A power supply unit.
Dimensions 70x100x62 mm.
Weight 0.2 Kg.