The UGC-M control unit is housed in a 6-module box for DIN rail and is provided with the following inputs:
• RJ45 8/8 PLUG connector for chip card or proximity card reader,
• RJ12 6/6 PLUG connector for badge or jack room activator;
• bathroom cord, flood sensor,
• digital input for “do not disturb” button,
• 3 programmable digital inputs for:
• window switch (NC or NO),
• courtesy light button (NO),
• door opening button from bed headboard (NO), switch,
• timed button (NO),
• infrared or dual-technology intrusion sensor (NC or NO),
• reset button to reset one or more of the following signallings: bathroom or flood alarm, room to clean, mini-bar to check.
• It is provided with 3 relay outputs with voltage-free contacts for 230Vac – 4(2) A loads to control:
• courtesy light switching-on or shutter opening, room electricity contactor,
• programmable AUX output for activation of one of the following devices:
• electric shutter closing,
• water valve closing in case of flood,
• ON/OFF controls or with software clock,
• timed activation with button.
A 12Vdc, max 1.2A voltage output for door lock activation and a SCR output for power supply of “do not disturb” luminons button are also available.
All connectors are removable with 5.08 pitch.
Data is transmitted over 2-wire UTP CAT.5 bus cable, RS 485 standard, with flashing led to check the correct communication between PC and units. Re-programmable microcontroller of flash type.
12Vac, 30VA power supply.
Dimensions: 106x100x60 mm.
Weight: 0.30 kg.